ZY Single-Stage Vacuum Transformer Oil Filtration Machines
This model is designed according to the nature of transformer insulating oils, so it can effectively remove gas, moisture, and solid impurities from new or used insulating fluids,improve the oil's dielectric strength and expands
the service life.
Technical Parameters
Index Name |
Unit |
ZY-10 |
ZY-20 |
ZY-30 |
ZY-50 |
ZY-100 |
ZY-150 |
ZY-200 |
ZY-300 |
|
Flow Rate |
L/H |
600 |
1200 |
1800 |
3000 |
6000 |
9000 |
12000 |
18000 |
|
Working Vacuum |
MPa |
-0.06~-0.095 |
||||||||
Working Pressure |
MPa |
≤ 0.4 |
||||||||
Temperature Range |
℃ |
20 ~ 80 |
||||||||
Dielectric Strength |
KV |
≥ 50 |
||||||||
Water Content |
ppm |
≤ 5 |
||||||||
Gas Content |
% |
≤ 0.2 |
||||||||
Particles Size |
micron |
≤ 1 |
||||||||
Power Supplier |
|
customizable |
||||||||
Working Noise |
dB(A) |
≤ 65~85 |
||||||||
Heating Power |
Kw |
15 |
15 |
15 |
30 |
48 |
60 |
72 |
90 |
|
Total Power |
Kw |
16.5 |
16.5 |
16.5 |
33.5 |
53 |
65 |
76 |
98 |
|
Inlet(Outlet) |
mm |
Φ25 |
Φ25 |
Φ25 |
Φ32 |
Φ42 |
Φ50 |
Φ50 |
Φ60 |
|
Weight |
kg |
230 |
250 |
270 |
300 |
500 |
700 |
900 |
1100 |
|
Dimension |
L |
mm |
1000 |
1000 |
1050 |
1200 |
1450 |
1600 |
1800 |
1900 |
W |
mm |
700 |
750 |
750 |
950 |
1000 |
1100 |
1200 |
1200 |
|
H |
mm |
1300 |
1400 |
1450 |
1500 |
1800 |
1800 |
1900 |
1900 |
|